Safety Related Parameters - Pepperl+Fuchs 2/209 Manual

Trip amplifier
Table of Contents

Advertisement

Trip Amplifier 2/209
Safety concept
9.2

Safety related parameters

9.2.1
Safety parameters for SIL2
In consultation with TÜV Rheinland, the PFH value for this device can be calculated as
EN
follows:
PFH = PFD
Configuration: 8 inputs (use in pairs for a physical value)
Device
PFH = 31.6 x 10
chain = 72.2 %)
Configuration: 4 inputs (use in pairs for a physical value)
Device
PFH = 16.67 x 10
chain = 38 %)
46
x 2 / proof test interval [h]; at 1 year test interval
avg
4 outputs
SSF
1-channel part
HFT = 0
Set  90 %
2/209
90.4 %
2/209
90.4 %
2/209
90.4 %
-4
x 2 / 8760 h = 72.2 x 10
2 outputs
SSF
1-channel part
HFT = 0
Set  90 %
2/209
90.7 %
2/209
90.7 %
2/209
90.7 %
2/209
99.5 %
-4
x 2 / 8760 h = 38 x 10
SSF
Safety
2-channel part
integrity
HFT = 1
level
Set  60 %
94.6 %
SIL2
94.6 %
SIL2
94.6 %
SIL2
-8
1/h (share of the logic in the safety
SSF
Safety
2-channel part
integrity
HFT = 1
level
Set  60 %
93.7 %
SIL2
93.7 %
SIL2
93.7 %
SIL2
90.4 %
SIL2
-8
1/h (share of the logic in the safety
PFD
Share of the
avg
logic in the
safety chain
7.9 %
7.9 x 10
-4
15.0 %
15.0 x 10
-4
31.6 %
31.6 x 10
-4
PFD
Share of the
avg
logic in the
safety chain
4.0 %
4.0 x 10
-4
7.9 %
7.9 x 10
-4
15.0 %
15.0 x 10
-4
31.7 %
31.7 x 10
-4
Proof test
interval [a]
0.3
0.5
1.0
Proof test
interval [a]
0.3
0.5
0.9
2.0