Environmental Specifications; Rpo Port Specifications - HPE G2 R5000 User Manual

3u ups
Table of Contents

Advertisement

Table 1: G2 R5000 battery runtimes
Load %
10
20
40
60
80
100
Table 2: G2 R6000 battery runtimes
Load %
10
20
40
60
80
100

Environmental specifications

Feature
Operating temperature
Nonoperating
temperature
Relative humidity
Operating altitude
Nonoperating altitude
Audible noise

RPO port specifications

The RPO port meets the requirements of NFPA Articles 645-10 and 645-11 for a Disconnecting Means.
Estimated battery
runtime (minutes)
73
42
17
9
5
3
Estimated battery
runtime (minutes)
57
34
14
7
5
3
Specification
0ºC to 40ºC (32ºF to 104ºF)
With batteries—0ºC to 40ºC (32ºF to 104ºF)
Without batteries—-15ºC to 60ºC (5ºF to 140ºF)
0-95% non condensing
Up to 3,000m (9,843ft) above sea level
Up to 10,000m (32,808ft) above sea level
Less than 45 dBA, normal operation
Runtime with one ERM
(minutes)
245
149
69
39
25
20
Runtime with one ERM
(minutes)
202
125
57
32
22
16
Runtime with four
ERMs (minutes)*
931
559
250
144
103
80
Runtime with four
ERMs (minutes)*
753
448
194
116
84
58
Specifications
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G2 r6000

Table of Contents