Specifications

UPS physical specifications

Parameter
Height
Depth
Width
Weight

ERM physical specifications

Parameter
Height
Depth
Width
Weight

UPS input specifications

UPS model
G2 R5000 4out
NA/JPN
G2 R5000 5out
NA/JPN
G2 R6000 INTL 50/60

UPS output specifications

UPS model
G2 R5000 4out
NA/JPN
G2 R5000 5out
NA/JPA
G2 R6000 INTL
Value
13.0cm (5.1in)
72.13cm (28.4in)
43.9cm (17.3in)
48kg (106lb)
Value
13.0cm (5.1in)
72.13cm (28.4in)
43.9cm (17.3in)
68kg (150lb)
Utility voltage
Available settings
frequency (Hz)
utility voltage (VAC)
50/60
200/208/220/230/240
50/60
200/208/220/230/240
200/208/220/230/240
Load segment
1
1
2
Branch circuit rating
(A)
30A
30A
32A
Output receptacles
2 x L6-20R/2 x L6-30R
4 x C19, 1x L6-30R Pigtail
4 x C13/4 x C19, 1x IEC 32A Pigtail
Line cord
Nondetachable
power cord with
NEMA L6-30 plug
Nondetachable
power cord with
NEMA L6-30 plug
Nondetachable
power cord with
IEC60309 3-pin 32A
IP44 plug