HPE G2 R5000 User Manual page 20

3u ups
Table of Contents

Advertisement

UPS power rating
5000VA
6000VA
Recommended cable cross-sections
Terminal position
L1
N (L2)
1
Copper wire, solid, or stranded.
Connecting the Input/Output
WARNING: Hewlett Packard Enterprise recommends that this connection is made only by a licensed
electrician.
20
Installation
Wire function
Terminal wire size
rating
Phase
4-16mm
G)
Neutral (phase)
Ground
Upstream circuit breaker
D curve—30A
D curve—32A
Minimum input
sire size
1
1
(12-6AW
6mm
(10AWG)
105°C (221°F)
1
10mm
(8AWG)
75°C (167°F)
Tightening torque
10lb in/1.13 Nm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G2 r6000