Controllers for top-class blast chillers, in split version that can be built into the unit, with 5- or 7-inch colour tft touch-screen graphic display in either vertical or horizontal format (84 pages)
Page 1
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Vcolor 818 Controller for “top-class” blast chillers, with colour touch-screen TFT graphic display, in split version and which can be integrated into the unit ENGLISH INSTALLER MANUAL ver. 1.1...
Page 2
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Important Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation. The following symbols support reading of the document: indicates a suggestion indicates a warning.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Index INTRODUCTION ........................... 5 Introduction ............................5 Summary table of the main features and the models available ..............6 DESCRIPTION ............................8 Description of the user interface ......................8 Description of the control module ......................
Page 4
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Memorisation of a program ......................... 51 Execution of a program ........................52 “FAVOURITES” FUNCTION ........................53 Foreword ............................53 Execution of a program ........................53 “HACCP” FUNCTION..........................54 Foreword ............................
INTRODUCTION Introduction Vcolor 818 is a controller with elegant design for the management of “top-class” blast chillers. It is available in split version and can be integrated both mechanically and aesthetically in the unit; the user interface consists of a colour touch-screen TFT graphic display and according to the IEC standards it guarantees an IP40 protection rating (IP65 in case of panel mounting with gasket 0027000007, to order separately), for easy cleaning.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Summary table of the main features and the models available The following table illustrates the main features of the device. “ / “ indicates the feature can be set via a configuration parameter.
Page 7
“programs” function • “HACCP” function • Notes: Configurable for dehumidifier or condenser fan. Configurable for pump down valve or evaporator fan. For further information, see chapter "TECHNICAL DATA"; for other models contact the EVCO sales network. page 7 of 94...
Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 DESCRIPTION Description of the user interface The following drawing illustrates the aspect of the Vcolor 818 user interface. The following table illustrates the meaning of Vcolor 818 user interface parts. Part...
Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Description of the control module The following drawing illustrates the aspect of the Vcolor 818 control module. The following table illustrates the meaning of the Vcolor 818 control module parts. Part Meaning...
Page 10
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 communication port with the user interface (signal and power supply) For further information, see the next chapters. page 10 of 94...
DIMENSIONS AND INSTALLATION User interface dimensions The following drawing illustrates the Vcolor 818 user interface dimensions; these are expressed in mm (in). Control module dimensions The following drawing illustrates the Vcolor 818 control module dimensions; these are expressed in mm (in).
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Installation warnings make sure that the device work conditions (temperature of use, humidity, etc.) lie within the limits indicated; see chapter 16 "TECHNICAL DATA" do not install the device near to any heat sources (heating elements, hot air ducts etc.), equipment containing powerful magnets (large diffusers, etc), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibrations or shocks.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 ELECTRIC CONNECTION Electric connection The following drawing illustrates the Vcolor 818 electric connection. The utility managed by the K7 output, depends on parameter u11, as follows: cabinet light (u11 = 0, pre-defined setting) UV light (u11 = 1).
Device commissioning Operate as follows: Connect the device power supply. if parameter E9 is set at 1, the device will display the EVCO splash screen for 10 s; After which it will go to the “stand-by” status.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the ON/STAND-BY key (1) and then press the highest interactive key on the left (2) to unlock the keyboard. Press and release the ON/STAND-BY (1) key.
Page 17
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 During the "run" state the device will display: if a temperature-controlled blast chilling or deep freezing operation is in progress, the temperature detected by the needle probe, the temperature of the cabinet, the name of the program, (if envisioned) and the time passed from the start of blast chilling or deep freezing.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Display of inputs and outputs status Operate as follows: Make sure that the instrument is in the “on” status. Make sure that the keyboard is not locked and that no procedure is in progress.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Defrosting activation in manual mode Operate as follows: Make sure the device is in the "on" status, that pre-cooling or storage cycle is in progress. Make sure that the keyboard is not locked and that no procedure is in progress.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Silencing the buzzer Operate as follows: Make sure no procedures are in progress Press and release the key. page 20 of 94...
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 OPERATION Foreword The device can manage the following operating cycles: temperature-controlled blast chilling and storage temperature-controlled hard blast chilling and storage time-controlled blast chilling and storage time-controlled hard blast chilling and storage...
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Temperature-controlled blast chilling and storage The temperature-controlled blast chilling and storage cycle is divided into the following two phases: blast chilling storage. On conclusion of a phase, the device passes automatically to the next.
Page 23
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the test is completed successfully, the cycle will be started. The maximum blast chilling duration count is started on condition that the temperature detected by the needle probe is below that established with parameter r15.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Temperature-controlled hard blast chilling and storage The temperature-controlled hard blast chilling and storage cycle is divided into the following three phases: blast chilling hard phase blast chilling storage.
Page 25
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the START/STOP key (1): the test to verify the correct insertion of the needle probe will be started; see paragraph 6.14 " Test for verification of the correct insertion of the needle probe".
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Parameter r10 establishes the work set-point during storage. If the temperature detected by the needle probe does not reach the blast chilling end temperature within the maximum blast chilling duration, blast chilling will not be completed successfully but will continue and the buzzer will be activated.
Page 27
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the blast chilling duration and the work set-point during blast chilling.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the duration of blast chilling. Parameter r10 establishes the work set-point during storage.
Page 29
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise them; these values can also be memorised through parameters r1 and r7.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Parameter r10 establishes the work set-point during storage. Continuous blast chilling Operate as indicated to start the cycle: Make sure the device is in the "on" status. Make sure that the keyboard is not locked and that no procedure is in progress.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the START/STOP key (1): the cycle will be started. During blast chilling the device displays the temperature of the cabinet, the program name (if envisioned) and the time passed since the start of blast chilling.
Page 32
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the deep freezing end temperature and the work set-point during deep freezing.
Page 33
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the temperature detected by the needle probe reaches the deep freezing end temperature within the maximum deep freezing duration, it means that deep freezing has been completed successfully, the device will automatically pass to storage and the buzzer will be activated for the period of time established with parameter AA.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Temperature-controlled soft deep freezing storage The temperature-controlled soft deep freezing and storage cycle is divided into the following three phases: deep freezing soft phase deep freezing storage. On conclusion of a phase, the device passes automatically to the next.
Page 35
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the test is completed successfully, the cycle will be started. The maximum deep freezing duration count is started on condition that the temperature detected by the needle probe is below that established with parameter r15.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 If the temperature detected by the needle probe does not reach the deep freezing end temperature within the maximum deep freezing duration, deep freezing will not be completed successfully but will continue and the buzzer will be activated.
Page 37
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the deep freezing duration and the work set-point during deep freezing.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 During deep freezing the device displays the temperature of the cabinet, the program name (if envisioned) and the duration of deep freezing. Parameter r11 establishes the work set-point during storage.
Page 39
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the MENU key and then press and release the key (4) or the key (5) to select the deep freezing duration and the work set-point during deep freezing.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Parameter r11 establishes the work set-point during storage. 6.11 Continuous deep freezing Operate as indicated to start the cycle: Make sure the device is in the "on" status.
Page 41
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the START/STOP key (1): the cycle will be started. During deep freezing the device displays the temperature of the cabinet, the program name (if envisioned) and the time passed since the start of deep freezing.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 6.12 Blast chilling/deep freezing intensity The device can manage the phase cut speed regulator for EVDFAN1 single phase fans (to be ordered separately); see paragraph 15.1 “phase cut speed regulator for EVDFAN1 single phase fans”.
Page 43
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 speed 1... 5 (can be memorised with the procedure given Deep freezing in paragraph speed 5 6.12.1 if selected before starting the operating cycle) speed established speed established...
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 6.12.1 Selecting the evaporator fan speed Operate as follows: Make sure the device is in the "on" status. Make sure that the keyboard is not locked and that no procedure is in progress.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Operate as follows to exit the procedure: Press and release the ESCAPE key or do not operate for 60 s. The fan is switched on at the selected speed after 5 s from release of the key (1) or the key (2).
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 6.14 Test for verification of the correct insertion of the needle probe If the needle probe is enabled, i.e. the parameter P3 is set at values different to 0; the temperature-controlled cycles are preceded by a test on two phases for the verification of the correct insertion of the needle probe.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key light (2) and then press and release the START/STOP key (3) The device will display the residual time of the UV light switch-on duration and the cabinet temperature.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Output K6 is activated at maximum for the time established with parameter u8 or until the temperature detected by the needle probe reaches that established with parameter u7; closing the door, i.e. the deactivation of the door micro switch input causes heating to be cut-off.
Page 49
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key (4) or the key (5) to select these values and press and release the key + (6) or the key - (7) to modify them.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 6.18 Data print-out The device can manage the PM 100A X9S001 module (to be ordered separately); see paragraph 14.5 "Print module PM 100A X9S001”. Using the module, it is possible to print information relative to the cabinet temperature, the temperature detected by the needle probe, at the alarms and at the errors (the latter two on condition that the alarm and/or the error is in progress on expiry of the print interval.
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 “PROGRAMS” FUNCTION Foreword The programs function can be used to memorise some settings in a program and start an operating cycle with the settings it has memorised. Up to 9 programs can be memorised.
Page 52
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the key (2) or the key (3) to select the program number and then press and release the key SET (6) in order to associate a name.
Page 53
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 “FAVOURITES” FUNCTION Foreword The favourites function can be used to execute a recently started program. It is possible to start up to 9 recently started programs Execution of a program Operate as follows: Make sure the device is in the "on"...
Page 54
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 “HACCP” FUNCTION Foreword Using the “HACCP” function, it is possible to memorise up to 9 events for each of the 3 HACCP alarms, after which the most recent event overwrites the oldest.
Page 55
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Display of information relative to the HACCP alarms Operate as follows: Make sure the device is in the "on" status. Make sure that the keyboard is not locked and that no procedure is in progress.
Page 56
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Deleting the information relative to the HACCP alarms Operate as follows: Make sure the device is in the "on" status. Make sure that the keyboard is not locked and that no procedure is in progress.
Page 57
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 COMPRESSOR OPERATING HOURS COUNT 10.1 Display of compressor operating hours Operate as follows: Make sure that the instrument is in the “on” status. Make sure that the keyboard is not locked and that no procedure is in progress.
Page 58
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 CONFIGURATION 11.1 Setting the real day and time Operate as follows: Make sure that the instrument is in the “on” status. Make sure that the keyboard is not locked and that no procedure is in progress.
Page 59
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.2 Setting the configuration parameters Operate as follows: Make sure that the instrument is in the “on” status. Make sure that the keyboard is not locked and that no procedure is in progress.
Page 60
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.3 Restoring the factory settings 11.3.1 Access to the procedure Operate as follows: Make sure that the instrument is in the “stand-by” status. Make sure that the keyboard is not locked and that no procedure is in progress.
Page 61
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.3.3 Deleting programs Operate as follows: Access to the; see paragraph 11.3.1 “Access to the procedure”. Press and release the key (1) to select “Programs”, repeatedly press and release the + key (2) to set “149”...
Page 62
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.3.5 Deleting the compressor operating hours Operate as follows: Access to the; see paragraph 11.3.1 “Access to the procedure”. Press and release the key (1) to select “rCH”, repeatedly press and release the + key (2) to set “149” and then press and release the SET key (3).
Page 63
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 11.4 List of configuration parameters The following table illustrates the meaning of the configuration parameters. The management of some inputs and outputs is subject to the value set with some parameters, as follows:...
Page 64
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 enabling the condenser probe - - - - = yes backlight configuration - - - - = low brightness = high brightness Par. Min. Max. Unit Default Main regulator °C/°F (1)
Page 65
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 work set-point during pre-cooling (cabinet temperature); °C/°F (1) see also parameter r0 end temperature of the temperature-controlled hard blast °C/°F (1) chilling phase (temperature detected by the needle probe)
Page 66
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Par. Min. Max. Unit Default Compressor protections minimum time between restoring the power supply after a power cut, occurring during an operating cycle and compressor switch-on minimum time between two consecutive compressor switch-...
Page 67
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 type of defrosting = electrical (the compressor will be switched off during defrosting, the defrosting output will be activated and the evaporator fan will be switched off) = hot gas (the compressor will be switched on during...
Page 68
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 duration of pre-dripping (only if parameter d1 is set at 1; the compressor and evaporator fan will be off during pre- dripping and the defrosting output will remain activated) Par.
Page 69
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 - - - - - - - - - - - - - - - - reserved Par. Min. Max. Unit Default Evaporator and condenser fan evaporator fan activity during pre-cooling, blast chilling and...
Page 70
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 condenser temperature above which the condenser fan is switched on (intended as “F11 + differential and on °C/°F (1) condition the compressor switched off); see also parameter F12 (4) (12)
Page 71
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 speed at which the evaporator fan is switched on during post blast chilling = speed established with parameter F18 (speed 1) - - - - = speed established with parameter F19 (speed 2)
Page 72
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 effect caused by the activation of the high pressure input = no effect = the compressor and the evaporator fan will be off and the condenser fan will be on. On expiry of the...
Page 73
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 switching on UV light for sterilisation cycle duration needle probe heating temperature (temperature °C/°F (1) detected by the needle probe); see also parameter u8 maximum duration of needle probe heating; see also...
Page 75
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 if on activation of defrosting, the previous compressor switched on at from a time shorter than that established with parameter d15, the compressor will remain on longer for the fraction of time necessary to complete this...
Page 76
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 USE OF THE USB PORT 12.1 Foreword Through the USB port it is possible to make the following operation (from and in a text document): upload and download of the configuration parameters upload and download of the programs download of the information relative to the HACCP alarms.
Page 77
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 To the end of the upload remove the USB peripheral from the USB port. 12.3 Upload and download of the programs To make the download of the programs operate as follows: Make sure the device is in the “stand-by”...
Page 78
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 To make the upload of the programs operate as follows: Make sure the device is in the “stand-by” status. Insert an USB peripheral in the USB serial port; make sure the peripheral contains the text document by name “recepits.bin”...
Page 79
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 12.4 Download of the information relative to the HACCP alarms To make the download of the information relative to the HACCP alarms operate as follows: Make sure the device is in the “stand-by” status.
Page 80
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Press and release the ESCAPE key or do not operate for 60 s. To the end of the download remove the USB peripheral from the USB port. To delete the information relative to the HACCP alarms see paragraph 9.3 “Deleting the information relative to the HACCP alarms”.
Page 81
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 ALARMS 13.1 Alarms The following table illustrates the meaning of the alarm codes. Code Meaning Temperature-controlled blast chilling or deep freezing not concluded within maximum duration alarm (HACCP alarm).
Page 82
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Low pressure alarm. Solutions: check the conditions of the low pressure input check the value of the parameter i8. Main consequences: the compressor and the evaporator fan will be off the alarm output will be activated.
Page 83
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 ERRORS 14.1 Errors The following table illustrates the meaning of the error codes. Code Meaning Cabinet probe error. Solutions: check the value of the parameter P0 check the integrity of the probe check the device-probe connection check the temperature of the cabinet.
Page 84
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Needle probe error 1. Solutions: the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 1. ain consequences if parameter P3 is set at 1: if the error occurs during the “stand-by”...
Page 85
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 ACCESSORIES 15.1 Phase cut speed regulator for single phase fans EVDFAN1 15.1.1 Introduction EVDFAN1 is a phase cut speed regulator for single phase fans. The regulator control signal is the PWM type, the same supplied by the controller analogue output.
Page 86
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 15.1.3 Dimensions The following drawing illustrates the EVDFAN1 dimensions; these are expressed in mm (in). 15.1.4 Connection to the device Operate as follows: Make sure that parameter F0 is set at 3.
Page 87
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 The following table illustrates the meaning of the PM 100A X9S001 parts. Part Meaning power supply RS-485 type serial port On/stand-by LED slot for paper advancement slot for manual paper advancement...
Page 88
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 15.2.4 Connection to the device Operate as follows: Make sure that parameter L0 is set at 1. Cut the device power supply off. Disconnect the PM 100A X9S001 power supply.
Page 89
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 TECHNICAL DATA 16.1 Technical data Purpose of the device: operating control device. Construction of control: electronic control device to be incorporated. user interface control module Box: self-extinguishing black.
Page 90
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 Humidity for use: from 10% to 90% relative humidity without condensate. Pollution situation: user interface control module Power supply: supplied from control 115… 230 VAC (±15%), 50/60 module.
Page 91
EVCO S.p.A. Vcolor 818 | Installer manual ver. 1.1 | Code 144VC818E114 8 outputs (electromechanical relays): 1 x 16 A res. output @ 250 VAC SPST type (K1) for compressor management 6 x 8 A res. outputs @ 250 VAC of which five SPST type for...
Page 93
This document is exclusive property of EVCO. Reproduction and disclosure are prohibited without express authorisation from EVCO. EVCO is not liable for any features, technical data and possible errors stated in this document or deriving from use of the same.