EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Vcolor 618 M & L Controller for retarding-proofing cabinets and rooms, with 5 or 7-inch colour TFT touch-screen graphic display, split version Installer Manual | ENGLISH...
Page 2
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Important Read this document carefully before installation and before using the device and take all the prescribed precautions. Keep this document with the device for future consultation.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Index INTRODUCTION ............ 4 Recipe book ............25 Introduction ............4 Pre-cooling ............25 Table listing the models available, their main features REGULATIONS ............ 27 and purchasing codes ..........
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 INTRODUCTION Introduction Vcolor 618 is a stylish controller for managing retarding-proofing cabinets and rooms. Available in split version, the controller consists of a 5-inch (M) or 7-inch (L) capacitive TFT touch-screen graphic display in glass, 65K colours, 800 x 480 pixel resolution and IP65 protection for easy cleaning.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Table listing the models available, their main features and purchasing codes The table below lists the models available. Vcolor 618 M Vcolor 618 L Models available...
Page 6
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 and manual conservation and proofing cycles Fan intensity management • • HACCP function • • "Programs" function • • Wi-Fi Connectivity (optional) • • For more information see the section 15 “TECHNICAL SPECIFICATIONS”.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 MEASUREMENTS AND INSTALLATION Vcolor 618 M user interface measurements The pictures below show the measurements of the 5-inch user interface; measurements are expressed in mm (inches).
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 User interface installation The picture below shows the installation of the user interface. The user interface installed from behind using threaded studs enables it to be placed flush with the panel thus making it fit perfectly with the design of the unit.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Precautions for electrical connection Do not use electric or pneumatic screwdrivers on the terminal blocks of the device. If the device has been moved from a cold to a warm place, the humidity may cause condensation to form inside. Wait about an hour before switching on the power.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 DESCRIPTION User interface description The picture below shows the front view of the Vcolor 618 L user interface. The table below describes the front parts of the user interface.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Control module description The diagram below shows the intended use of the control module connectors. PART DESCRIPTION control module power supply K4 and K3 relays...
Make the electrical connection as shown in section 3 ELECTRICAL CONNECTION. Connect the power supply to the device: if parameter E9 is set at 1 (default), the device will show the EVCO splash screen for 10 seconds; if the parameter is set at 0, a system loading screen will be shown:...
Page 15
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Par. Min. Max. Unit Default Type of probe - - - - Enable evaporator probe - - - - Disabled Enabled Enable condenser probe - - - -...
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 NAVIGATION Initial information Navigating the menus is intuitive, based on touch technology. To enter into a procedure touch the menu or the corresponding icon To exit the procedure and, in general, to return to the previous level, press the Back...
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Run screen Once a manual or automatic cycle has been started up, the Run screen will appear for the type of cycle selected. MANUAL REFRIGERATION...
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 6.3.2 Function keys While a manual or automatic cycle is being run, the lower part of the screen displays the function keys, which are as follows.
Page 19
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 6.5.1 Service This option gives access to the following menu RECORDINGS SET-UP This enables selection of the variables to be recorded for the HACCP history.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 AN OVERVIEW OF THE FUNCTIONS Automatic and manual cycles The controller provides complete control for retarding-proofing cabinets or rooms for bread or pastry-making by managing the complete dough retarding-proofing cycle automatically.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 The duration in hours and minutes and the evaporator fan speed are set by the end-user. BAKING DELAY phase The baking delay phase is always disabled but it can be enabled, either when the cycle is being set up or while it is in progress, by the end-user.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 MAIN FUNCTIONS Manual cycle This area grants access to manual REFRIGERATION or HEATING cycles. Before starting up the required cycle, press the screen inside the coloured area (blue for REFRIGERATION and red for HEATING) to access all the functions for changing the setpoints for the cycles in question.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Automatic cycle 8.2.1 Start-up and interruption of an automatic cycle This area grants access to the following screen displaying all the phases making up a RETARDING-PROOFING cycle: blocking, conservation, re-awakening, proofing and baking delay (see section 7 FUNCTIONS).
Page 24
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Once OK has been pressed each time to confirm the changes, these will be saved and used as the settings for the automatic cycle which is started up by pressing the area.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Recipe book This area grants access to the MY RECIPES screen listing the automatic retarding-proofing cycles saved with the name by the user, following the procedure described in the previous section 7.7.3. Users can save up to 100 recipes.
Page 26
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 page...
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 REGULATIONS Pre-cooling The purpose of the pre-cooling cycle is to bring the cabinet to a certain temperature before selecting and running a retarding-proofing cycle. During a pre-cooling cycle the compressor, condenser fans, pump-down solenoid valve (if enabled) and evaporator fan are working to reach the set temperature.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Humidity regulation In all phases where this is required, the humidity is regulated with a humidity transducer enabled in the neutral zone in which two values are set one above and one below the humidity setpoint, thus creating a zone inside which the loads for humidification and dehumidification are not activated.
Page 29
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 If parameter E12 is set at 2, the generator output will only be active when the humidity falls below the neutral zone value (set by parameter rU9) beyond the threshold set by rU8 (humidification differential).
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 10 LOAD MANAGEMENT 10.1 Compressor management Activation of the compressor depends on the length of the delay between two switch-ons (parameter C1), on the minimum duration of the compressor-off time (parameter C2), on the delayed switch-on of the compressor from the device power-on (parameter C0) and on the minimum duration of the compressor-on time (parameter C3).
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 10.4 Defrost management Defrost is active during the automatic BLOCKING and CONSERVATION phases and during the MANUAL REFRIGERATION phase and it can be either automatic (time intervals) or manual. Manual defrost can be activated by accessing the relevant menu on the On/standby...
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 10.7.2 Managing the humidifier output with a transducer and a humidifier with a steamer (rU0 = 0, E12 = 0) The humidifier output is activated when the humidity value inside the cabinet falls below the neutral zone value (rU9) beyond the threshold set by the humidification differential (rU8).
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 11 MANAGING THE USB PORT The USB port provides the following functions: download to a USB flash drive the data relating to the cycles performed (HACCP history)
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 12 ALARMS An alarm event is signalled by a prolonged buzzer sound and it can be seen when the icon appears on the upper part of the screen.
Page 35
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 All loads are deactivated Power failure during a cycle run alarm. POWER FAILURE To correct Check the device-power supply connection. Condenser overheat alarm. To correct...
Page 36
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Check the device-transducer connection. Check cabinet relative humidity. Main consequences if parameter rU0 is set to 0: If the error happens during “stand-by”, it will not be possible to start up humidity management cycles.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 13 PARAMETERS The table below describes the configuration parameters of the device. Par. Min. Max. Unit Default Analogue inputs °C Cabinet probe offset °C Evaporator probe offset °C...
Page 38
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Percentage increase for the 2 conservation step (out of a total of 100%) Percentage increase for the 3 conservation step (out of a total of...
Page 39
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Percentage increase for the 2 proofing step (out of a total of 100%) Percentage increase for the 3 proofing step (out of a total of 100%)
Page 40
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 proofing and baking delay phases Condensation temperature above which the condenser overheat alarm °C sounds Condensation temperature above which the compressor locked alarm °C sounds Compressor locked alarm delay Par.
Page 41
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Evaporator fan activity during the re-awakening phase - - - - parallel function with the main loads continuous function Evaporator fan activity during the proofing phase...
Page 42
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 -1 = alarm not signalled Effect caused by activation of the high pressure input no effect - - - - The compressor and evaporator fan are switched off, the...
Page 43
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 relevant) With u3 = 1 dehumidification will be managed automatically by activation of the refrigeration plant Serial communication (serial port type RS-485 with MODBUS Par.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 ACCESSORIES 14.1 Safety transformer (ECTSFD004) The transformer can power the Vcolor 618 L user interface. 14.2 Non-optoisolated RS-485/USB serial interface (EVIF20SUXI) Makes it possible to connect to the Parameters Manager setup software system.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 14.6 USB flash drive (EVUSB4096M) Makes possible configuration upload and download. 4GB of memory. 14.7 Graphic synoptic device (EVC25T00X7XXX04) The graphic synoptic device displays the process status instantly and intuitively.
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 TECHNICAL SPECIFICATIONS 15.1 Technical specifications Purpose of the control device Function controller Construction of the control device Built-in electronic device user interface control module Container Open frame board behind glass.
Page 47
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 EN 60730-1 EMC standards IEC 60730-1. user interface control module Vcolor 618 M: Power supply powered by the control module. 115... 230 VAC (±15%), 50 / 60 Hz Vcolor 618 L: (±3 Hz), 10 VA max.
Page 48
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 1 16 A res. @ 250 VAC type SPST (K1) output for managing the compressor 1 8 A res. @ 250 VAC type SPDT (K5) output for managing defrost 1 8 A res.
Page 49
EVCO S.p.A. Vcolor 618 M & L | Installer manual ver. 2.0 | Code 144VC618E204 Vcolor 618 M & L Controller for retarding-proofing cabinets and rooms, with 5 or 7-inch colour TFT touch-screen graphic display, in split version Installer manual ver. 2.0...