Displayed Ser-
Error number 333
vice Codes
Over current
(continued)
Cause:
Remedy:
Error number 334
Internal err
Cause:
Remedy:
Error numbers 335 - 337
Internal err
Cause:
Remedy:
Error number 391
Display lost
Cause:
Remedy:
Error number 392
Display fault
Cause:
Remedy:
Error number 393
Old software
Cause:
Remedy:
Error number 401
Slave fault
Cause:
Remedy:
Error number 402
Sync lost
Cause:
Remedy:
Error number 403
Sync lost
Cause:
Remedy:
Error number 404
No slave
Cause:
Remedy:
Error number 405
Old firmware
Cause:
Remedy:
Error number 406
Ph cfg err
Cause:
Remedy:
Short circuit at AC output
Disconnect load, correct short circuit
Device error
Inform service
Device error
Inform service
Communication with display is not possible
Inform service
Display error
Turn device off/on
AC processor software is incompatible with new firmware display
processor
Update software (service)
The master device has detected an error in a slave device in multi-
phase operation
Correct error at slave device
Synchronization signal from master device has not been received
multiple times
Check communication connection
A reset was triggered at the parallel bus
Device will correct error automatically
Error in communication setup in multi-device operation
Check setup settings and communication connections and correct if
necessary
Configuration error after service
Carry out firmware update
Incorrect phase system setting
Check device settings and communication connections