Installation
1
Wiring
1.4 Wiring
1.4.1 Electrical grounding
Situation
Consequences
8 | 22
Siemens
Building Technologies
Note the following grounding situation of the QBM97.
Power-
supply
24V
Transformer
●
QBM97 uses a non isolated RS485-Interface
●
The reference of RS485 transceiver is connected to GND
●
all GND pins are on the same potential
●
if the Climatix controller and QBM97 are connected to the same power source,
take care to avoid miswiring between 24 V input and GND
The document "Modbus communication" (J3960) provides profound information
on Modbus grounding.
REF B- A+
M
Not isolated RS485
≂
0V
Sensor module
Earth
A6V11478123_en_a
2019-02-01