Fault Detection, Correction Or Reset - Siemens QBM97 Series User Manual

Modbus air pressure sensor with i/o extension
Table of Contents

Advertisement

Commissioning
2

Fault detection, correction or reset

2.2 Fault detection, correction or reset
14 | 22
Siemens
Building Technologies
Detect and correct faults
The status LED blinking red indicates a failure or wrong configuration
Read out Error Code (register 4x0002) value 0...11 (see table below)
Further information contain
Status register of pressure sensor
Status register of universal inputs
Value
Error code (register
4x0002)
0
no error
1
no sensor
2
overload
3
underload
4
open loop
5
short time overload
6
no output signal
7
other error
8
calculation error
9
extended error
10
EEPROM
protection active
11
configuration error
Reset to factory setting
Use the push button to do a reset to factory setting. The Sensor is reset to
delivered setting. Factory settings are listed in the register list "Modbus registers
[➙ 16]" – default values.
Hold the push button for 20...30 seconds.
Reliability pressure
sensor (register 4x0004
+ 4x0006)
no error
disruption in operation
overload
negative pressure
zero point reset required
configuration error
Reliability analog
inputs (register
4x0008 + 4x0010)
no error
sensor not
connected
temperature >
150ºC
temperature < -
50ºC
short time overload
configuration error
A6V11478123_en_a
2019-02-01