Applied Systems Engineering ASE2000 User Manual page 193

Communication test set
Hide thumbs Also See for ASE2000:
Table of Contents

Advertisement

Quality shows quality codes applicable to this ASDU type
Increment specifies an amount to add to the value after each ASE2000-generated response.
The new value is used in the next response. Values are incremented to a maximum, then
decremented by the same amount to a minimum. The cycle is repeated. Maximum and minimum
values are set by the ASE2000. They can be viewed and changed from the Properties dialog
and Point tab
Totals
BCR is the point value
Quality shows quality codes applicable to this ASDU type
Increment specifies an amount to add to the value after each ASE2000-generated response.
The new value is used in the next response. Values wrap to 0 after exceeding a maximum. The
maximum is set by the ASE2000 and can be observed and changed from the Properties dialog
and Point tab
Protection Events
SPE identifies the type of event
Quality shows quality codes applicable to this ASDU type
ASE2000 V2 Communication Test Set User Manual
193