Huawei SUN2000-50KTL-M0 User Manual page 90

Hide thumbs Also See for SUN2000-50KTL-M0:
Table of Contents

Advertisement

SUN2000-(50KTL-M0, 70KTL-INM0)
User Manual (India Edition)
Parameter List
Parameter
Grid code
Isolation
Output mode
PQ mode
Auto start upon grid
recovery
Grid connection
duration after grid
recovery (s)
Grid reconnection
voltage upper limit (V)
Grid reconnection
voltage lower limit (V)
Grid reconnection
frequency upper limit
(Hz)
Grid reconnection
frequency lower limit
(Hz)
Issue 03 (2019-07-30)
Vn represents the rated voltage and Fn represents the rated frequency.
Description
Set this parameter based on the grid code of the
country or region where the SUN2000 is used and
the SUN2000 application scenario.
Set the working mode of the inverter based on the
grounding status at DC side and the connection to
the power grid.
Indicates whether the SUN2000 output has a neutral
wire.
If this parameter is set to PQ mode 1, the maximum
active power equals the maximum apparent power.
If it is set to PQ mode 2, the maximum active
power equals the rated active power.
Specifies whether to allow the SUN2000 to
automatically start after the power grid recovers.
Specifies the waiting time for SUN2000 restart after
the power grid recovers.
The standards of certain countries and regions
require that the SUN2000 must not export power to
the power grid again when the grid voltage exceeds
the value of Grid reconnection voltage upper
limit after the SUN2000 shuts down due to a fault.
The standards of certain countries and regions
require that the SUN2000 must not export power to
the power grid again when the grid voltage is below
the value of Grid reconnection voltage lower limit
after the SUN2000 shuts down due to a fault.
The standards of certain countries and regions
require that the SUN2000 must not export power to
the power grid again when the grid frequency
exceeds the value of Grid reconnection frequency
upper limit after the SUN2000 shuts down due to a
fault.
The standards of certain countries and regions
require that the SUN2000 must not export power to
the power grid again when the grid frequency is
below the value of Grid reconnection frequency
lower limit after the SUN2000 shuts down due to a
fault.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Remarks
N/A
N/A
Supported by the
SUN2000-50KTL-M0 only.
Supported by the
SUN2000-50KTL-M0 only.
N/A
N/A
N/A
84