CHAPTER 5 - CTRLMAX OPERATION

5.10.3 Automatic Reset Blocking Lockouts

Code
Lockout Message
E7
High Flue Temperature
E12
Internal Control Fault
E25
Internal Control Fault
E32
DHW Sensor Shorted
E33
DHW Sensor Open
E34
Low Voltage
E37
Low Water
E45
Flue Sensor Shorted
E46
Flue Sensor Open
E76
External Limit Open
E77
High Mix Circuit Temperature
E78
Mix Circuit Sensor Shorted
E79
Mix Circuit Sensor Open
E81
Sensor Drift
E82
Delta T Protection
E89
Incorrect Setting
E90
Firmware Mismatch
E91
System Sensor Shorted
E92
System Sensor Open
E93
Outdoor Sensor Shorted
E94
Internal Display Fault
E95
Supply Sensor Error
E96
Outdoor Sensor Open
E97
Cascade Mismatch
E98
Cascade Bus Error
E99
Controller Bus Error
Description
Flue temperature exceeds high limit.
EEPROM misconfiguration.
CRC check error.
A short circuit has been detected in the DHW temperature sensor circuit.
An open circuit has been detected in the DHW temperature sensor circuit.
Line voltage has fallen below an acceptable operating level.
Water pressure has fallen below 7.2 psi.
A short circuit has been detected in the boiler flue temperature sensor circuit.
An open circuit has been detected in the boiler flue temperature sensor circuit.
An external automatic reset boiler limit has opened.
Mix circuit temperature exceeds Mix zone high limit setting.
A short circuit has been detected in the mix circuit temperature sensor circuit.
An open circuit has been detected in the mix circuit temperature sensor circuit.
Supply and return temperatures are not equal.
Excessive difference between the boiler supply and return temperatures.
A parameter setting is in conflict with another setting.
Control module and display firmware versions are incompatible.
A short circuit has been detected in the system temperature sensor circuit.
An open circuit has been detected in the system temperature sensor circuit.
A short circuit has been detected in the outdoor temperature sensor circuit.
Display memory error.
Supply sensor reading is invalid.
An open circuit has been detected in the outdoor temperature sensor circuit.
Cascade configuration has changed.
Communication with other boilers has been lost.
Communication between boiler display and control module has been lost.
23