Download Print this page
TriangleTube Instinct Solo Series Conversion Instructions

TriangleTube Instinct Solo Series Conversion Instructions

Natural to propane conversion instructions
Hide thumbs Also See for Instinct Solo Series:

Advertisement

Quick Links

Natural to Propane Conversion Instructions
Kit Part Number
INSRKIT08 (Solo 110)
INSRKIT10 (Solo/Combi 155)
INSRKIT12 (Solo/Combi 199)
Kit Includes
Rating Label
Conversion Label
(1) Propane Gas Venturi
Acoustic Foam
WARNING
!
Indicates a potentially hazardous situation which,
if ignored, can result in serious injury or substan-
tial property damage.
NOTICE
When converting the appliace from Natural to Propane ensure that the conversion is completed before fully installing the
air inlet piping.
WARNING
!
For your safety, turn off electrical power supply
at service panel and allow unit to cool before pro-
ceeding to avoid possible electrical shock and
scald hazard. Failure to do so can cause severe
personal injury or death.
NOTICE
Upon completion of the conversion from Natural to Pro-
pane, affix the new rating label included in the kit to the
unit adjacent to the existing rating label. DO NOT affix
the new label over the existing rating label. Add propane
conversion labeling to the gas valve.
223042 A02
Revision Date: 07/2019
Instinct Solo/Combi
Recommended Tools
Adjustable Wrench / 10 mm Socket & Ratchet
Phillips Head Screwdriver
Flat Head Screwdriver
Calibrated Combustion Analyzer
NOTICE
Indicates special instructions on installation, operation
or maintenance, which are important to equipment
but not related to personal injury hazards.
WARNING
!
Failure to follow instructions below can result in
severe personal injury or damage if ignored.
Instructions are for a qualified installer/ ser-
vice technician only.
Read all instructions before proceeding.
Follow instructions in proper order.
NOTICE
These instructions cover NG to LP conversion for Instinct
boilers only. Each kit is supplied with one venturi suitable
for use with that particular boiler model.
2019-18 Instinct NG to LP Conversion

Advertisement

loading
Need help?

Need help?

Do you have a question about the Instinct Solo Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TriangleTube Instinct Solo Series

  • Page 1 Instinct Solo/Combi Natural to Propane Conversion Instructions Kit Part Number Recommended Tools • INSRKIT08 (Solo 110) • Adjustable Wrench / 10 mm Socket & Ratchet • INSRKIT10 (Solo/Combi 155) • Phillips Head Screwdriver • INSRKIT12 (Solo/Combi 199) • Flat Head Screwdriver •...
  • Page 2: Electrical Shock Hazard

    INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 1. Preliminary Instructions: 2. Install the Acoustic Foam (supplied); 1. Verify that the \venturi replacement kit is correct 1. Cut a 7" length of 3" diameter air inlet piping. for the model of boiler. See page 1. 2.
  • Page 3 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 3. Removal of Natural Gas Venturi 1. Remove the silicone tube from the air inlet elbow, then remove the air inlet elbow. 2. Rotate the venturi interface approximately 60° clockwise to release the clamping mechanism and remove the venturi interface.
  • Page 4 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 6. Attach the propane conversion label to the gas WARNING valve and the propane conversion rating label next to the existing rating label Failure to retain the O-ring gasket between the ventu- ri and the blower will cause an improper seal resulting 7.
  • Page 5 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 5. Combustion Test and Adjustments NOTICE NOTICE An adequate CH load must be present to dissipate the heat generated during the combustion test. If an adequate CH load The installer MUST perform a complete combustion check is not available, an indirect water heater can be used to dis- to ensure the following combustion levels are met at high and low input firing rates and the burner is operating at op-...
  • Page 6 INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS Table 1: Combustion Settings Propane (All Models) Range 10.4 - 11.0% Range 5.1 - 4.2% CO Max 200 ppm Range 10.4 - 11.0% Ensure CO values measured are less than or equal to High Fire CO measurements Range 5.1 - 4.2%...