Technical Data - ABB RELION 615 Series Product Manual

Transformer protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Transformer Protection and Control
RET615
Product version: 5.0 FP1

18. Technical data

Table 6. Dimensions
Description
Width
Height
Depth
Weight
Table 7. Power supply
Description
Nominal auxiliary voltage U
n
Maximum interruption time in the auxiliary DC
voltage without resetting the relay
Auxiliary voltage variation
Start-up threshold
Burden of auxiliary voltage supply under
quiescent (P
)/operating condition
q
Ripple in the DC auxiliary voltage
Fuse type
Table 8. Energizing inputs
Description
Rated frequency
Current inputs
Voltage inputs
1)
Residual current and/or phase current
28
Value
Frame
Case
Frame
Case
Complete protection relay
Plug-in unit only
Type 1
100, 110, 120, 220, 240 V AC, 50 and 60 Hz
48, 60, 110, 125, 220, 250 V DC
50 ms at U
n
38...110% of U
(38...264 V AC)
n
80...120% of U
(38.4...300 V DC)
n
DC <13.0 W (nominal)/<18.0 W (max.)
AC <16.0 W (nominal)/<21.0 W (max.)
Max 15% of the DC value (at frequency of 100 Hz)
T4A/250 V
Rated current, I
n
Thermal withstand capability:
• Continuously
• For 1 s
Dynamic current withstand:
• Half-wave value
Input impedance
Rated voltage
Voltage withstand:
• Continuous
• For 10 s
Burden at rated voltage
177 mm
164 mm
177 mm (4U)
160 mm
201 mm (153 + 48 mm)
4.1 kg
2.1 kg
Type 2
24, 30, 48, 60 V DC
50...120% of U
19.2 V DC (24 V DC × 80%)
DC <13.0 W (nominal)/<18.0 W (max.)
Value
50/60 Hz ± 5 Hz
1)
1/5 A
20 A
500 A
1250 A
<20 mΩ
60...210 V AC
240 V AC
360 V AC
<0.05 VA
1MRS756891 M
(12...72 V DC)
n
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret615

Table of Contents