ABB RELION 615 Series Product Manual page 34

Transformer protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Transformer Protection and Control
RET615
Product version: 5.0 FP1
Table 22. Electromagnetic compatibility tests, continued
Description
Power frequency immunity test
• Common mode
• Differential mode
Conducted common mode disturbances
Emission tests
• Conducted
0.15...0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Table 23. Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance measurements
Protective bonding resistance
Table 24. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
34
Type test value
Binary inputs only
300 V rms
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak, measured at 10 m
distance
<47 dB (µV/m) quasi peak, measured at 10 m
distance
<76 dB (µV/m) peak
<56 dB (µV/m) average, measured at 3 m
distance
<80 dB (µV/m) peak
<60 dB (µV/m) average, measured at 3 m
distance
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
>100 MΩ, 500 V DC
<0.1 Ω, 4 A, 60 s
Requirement
Class 2
Class 2
Class 2
1MRS756891 M
Reference
IEC 61000-4-16
IEC 60255-26, class A
IEC 61000-4-16
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
Reference
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret615

Table of Contents