ABB RELION 615 Series Product Manual page 45

Transformer protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Transformer Protection and Control
RET615
Product version: 5.0 FP1
Table 54. Multipurpose protection (MAPGAPC) main settings
Parameter
Start value
Operate delay time
Operation mode
Table 55. Operation characteristics
Parameter
Operating curve type
Operating curve type (voltage protection)
ABB
Function
MAPGAPC
MAPGAPC
MAPGAPC
Value (Range)
-10000.0...10000.0
0...200000 ms
1 = Over
2 = Under
Value (Range)
1 = ANSI Ext. inv.
2 = ANSI Very. inv.
3 = ANSI Norm. inv.
4 = ANSI Mod inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv
15 = IEC Def. Time
17 = Programmable
18 = RI type
19 = RD type
5 = ANSI Def. Time
15 = IEC Def. Time
17 = Inv. Curve A
18 = Inv. Curve B
19 = Inv. Curve C
20 = Programmable
21 = Inv. Curve A
22 = Inv. Curve B
23 = Programmable
1MRS756891 M
Step
0.1
100
-
45