ABB RELION 615 Series Product Manual page 17

Transformer protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Transformer Protection and Control
RET615
Product version: 5.0 FP1
GUID-AB31C909-F38E-4885-AFEE-E2EEE3675263 V4 EN
Figure 12.
Protection of a two-winding power transformer with RET615 standard configuration E
Figure 12
illustrates the protection of a two-winding power
transformer with RET615 standard configuration. The main
protection used in this application example is transformer
differential protection. Restricted earth-fault protection with
numerical low-impedance principle is applied on the
ABB
3U
Uo
A
U12 0. 0 kV
P 0.00 kW
3I (HV)
Q 0.00 kVAr
IL2 0 A
I
ESC
Clear
O
R
L
Io (HV)
RTD
3U
3I (LV)
transformer's HV side. The RTD inputs of RET615 are utilized
for monitoring the oil temperature and oil level of the
transformer. Additionally, REU615 with the standard
configuration B is used as automatic voltage regulator for the
on-load tap changer of the transformer.
RET615
Std. conf.
E
ANSI
IEC
27/59
3U</3U>
49T
3Ith>T
50L/50NL
ARC
50P/51P
3I>>>
51P/51N
3I/Io
87NL
dIoLo>
87T
3dI>T
A
REU615
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
I
ESC
Clear
Std. conf.
B
O
R
L
ANSI
IEC
27/59
3U</3U>
50P/51P
3I>>>
51P/51N
3I/Io
84M
TPOSM
90V
COLTC
1MRS756891 M
17