Transformer Protection and Control
RET615
Product version: 5.0 FP1
Table 22. Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance test
• Common mode
• Differential mode
3 MHz, 10 MHz and 30 MHz burst disturbance
test
• Common mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference test
Fast transient disturbance test
• All ports
Surge immunity test
• Communication
• Other ports
Power frequency (50 Hz) magnetic field
immunity test
• Continuous
• 1...3 s
Pulse magnetic field immunity test
Damped oscillatory magnetic field immunity test
• 2 s
• 1 MHz
Voltage dips and short interruptions
ABB
Type test value
2.5 kV
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f = 150 kHz...80 MHz
10 V/m (rms)
f = 80...2700 MHz
10 V/m
f = 900 MHz
20 V/m (rms)
f = 80...1000 MHz
4 kV
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
6.4/16 µs
100 A/m
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
1MRS756891 M
Reference
IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2002
IEC 61000-4-18
IEC 60255-26, class III
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
IEC 61000-4-6
IEC 60255-26, class III
IEC 61000-4-3
IEC 60255-26, class III
ENV 50204
IEC 60255-26, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
IEC 61000-4-5
IEC 60255-26
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
33