Daikin GCU compact Series Installation And Operating Instructions Manual page 75

Table of Contents

Advertisement

P
Circulation pump (optional)
Z
3UVB1
3-way mixer valve
3UV DHW
3-way distribution valve
AUX
Output for special functions
RoCon U1
Room station (optional)
RoCon M1
Mixer circuit control (optional)
FLS
Flow sensor (boiler circuit)
EXT
Input for external operating mode switching
EBA
Floating switch contact for external heat request
t
Inflow temperature sensor (boiler circuit)
V1
t
Internal mixer sensor = inflow temperature sensor (heating
V2
circuit)
t
Return flow temperature sensor
R2
t
Outside temperature sensor
AU
t
Storage tank temperature sensor
DHW
RT/RT-E
Room thermostat (optional)
STBK
Safety temperature limiter
RoCon BE1
Circuit board
RJ45 CAN
BUS – control panel connection
S3
DIP switch (device type)
S5
DIP switch (1=on; 2,3,4=off)
RoCon B1
Control panel
DS
Pressure sensor
P
Heating circulation pump
K
PWM (P
)
Speed controller for PK
K
Q
Device main switch
1
F
Fuse
1
EL1
Ignition electrode
EL2
Ionisation electrode
STBK
Safety temperature limiter
Burner blower mains connection
BF
BF-PWM
Burner blower speed regulation
GMV
Voltage supply for gas solenoid valve
GPV
Voltage supply for plunger coil
TRA1
Ignition transformer
CM 434
Automatic combustion control
J1
3-pin circuit board connector with mains pump cable
J2
4-pin circuit board connector: Connection of 3-way mixer
valve 3UVB1
J3
6-pin circuit board connector (AUX connection for special
functions)
J4
3-pin circuit board connector (not occupied)
J5
3-pin circuit board connector with pressure sensor cable
J6
4-pin circuit board connector with clamped mains cable and
earthing slots
J7
2-pin circuit board connector with PWM signal cable for ex-
ternal heating circulation pump
J8
12-pin circuit board connector for connecting sensors and
control lines
J9
5-pin circuit board connector (not assigned)
J10
3-pin circuit board connector with mains cable for combus-
tion control CM 434
J11
5-pin circuit board connector with communication cable for
combustion control CM 434
J12
4-pin circuit board connector: Connection of 3-way distribu-
tion valve 3UV DHW
J13
4-pin circuit board connector for connection of additional
controller components (CAN bus)
J14
3-pin circuit board connector for clamping a circulation
pump
J15
4-pin circuit board connector with switch cable
J16
4-pin circuit board connector for connection of a room ther-
mostat (digital request contact)
Mains voltage 230 V, 50 Hz
Gas Combi Unit
Floor-standing gas condensing boiler with integrated heat storage
008.1543899_02 – 04/2019 – EN