Page 1
RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER Mounting and operating instructions...
Page 2
INTENDED AREA OF USE TECHNICAL DATA STANDARDS OPERATIONAL DIAGRAM MOUNTING & OPERATING INSTRUCTIONS IN STEPS OPERATING INSTRUCTIONS VERIFICATION OF INSTALLATION INSTRUCTIONS MODBUS REGISTER MAPS TRANSPORT AND STORAGE WARRANTY AND RESTRICTIONS MAINTENANCE MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 2 - 11 www.sentera.eu...
In case there are any questions that are not answered, please contact your technical support or consult a professional. MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 3 - 11 www.sentera.eu...
RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER PRODUCT DESCRIPTION The RMFPM-2R are multifunctional room controllers featuring adjustable temperature, relative humidity and CO setpoints. They are Power over Modbus supplied and all parameters and the output are accessible via Modbus RTU. ARTICLE CODES Code...
Follow these steps: Using a flat screwdriver, remove the front white cover by releasing the snap-fits on its both sides (See Fig. 1 Snap-fits release). MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 5 - 11 www.sentera.eu back to the table of contents...
Page 6
To assure correct communication, the NBT needs to be activated in only two devices on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or Sensistant (Holding register 9). MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 6 - 11 www.sentera.eu...
Page 7
When the red LED is on, the measured value (temperature, relative humidity or ) is below the minimum measurement range value or above the maximum value. Blinking red LED indicates loss of communication with a sensor (Fig. 6 - 3). MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 7 - 11 www.sentera.eu...
After switching on the power supply one of the LEDs lights up according to the status of the measured variable. If this is not the case, check the connections. MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 8 - 11 www.sentera.eu...
Flag that shows if the communication with the 0 = No Ambient light sensor fault unsigned int 0—1 ambient light sensor is lost 1 = Yes MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 9 - 11 www.sentera.eu back to the table of contents...
Page 10
0 Maximum output 60—100 unsigned int Set maximum value of output signal in percentage 60 = 60 % value default: 100 MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 10 - 11 www.sentera.eu back to the table of contents...
In case of heavy pollution, clean with a non-aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry. MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019 11 - 11 www.sentera.eu...