Pepperl+Fuchs ICDM-RX/MOD Manual page 29

Modbus router user
Table of Contents

Advertisement

ICDM-RX/MOD User Manual
Overview
To implement this Device ID Mapping example, the following web page configuration entries are required on the
Modbus Alias Device ID Configuration page, which is accessed by clicking Modbus | Alias Configuration.
Where:
Parameter
Rx Device
Alias Device ID
Modbus/TCP Master
Modbus Serial Master
Modbus over TCP Master
Type
Configuration
The original, or pre-alias, device ID received from Modbus
(1-255)
master(s). Required.
Configuration
The corresponding slave device ID. Required.
(1-255)
Configuration (yes/
Enables the Alias conversion from Modbus/TCP masters.
no)
Must be enabled if Modbus/TCP master(s) are present.
Configuration (yes/
Enables the Alias conversion from serial Modbus masters.
no)
Must be enabled if serial Modbus master(s) are present.
Enables the Alias conversion from Modbus over Ethernet
Configuration (yes/
TCP/IP masters. Must be enabled if Modbus over Ethernet
no)
TCP/IP master(s) are present.
Description