curve type and performs a trip after the operation delay time. The direction of the protection is
determined using the direction angle value under protection settings.
Directional Active Over Power is indicated by P>, P>> in IEC 60617; PI_PDOP_1 ve
PI_PDOP_2 in IEC 61850; 32OP-I-1 ve 32OP-I-2 in IEEE/ANSI Standards
EŞİK-1 PI_PDOP_1
EŞİK-2 PI_PDOP_2
The menu view is as follows. The menu consists of six lines.
The settings that can be made in the menu are described below.
4.3.5.1.1
Protection
It can be selected 'Active' or 'Passive'.According to the treshold situation, the protection is
activated in the active state and disabled in the passive state
4.3.5.1.2
Start Value
Directional Active Over Power
IEC 61850
Directional Active Over Power Function Symbols
Directional Active Over Power Protection Display
IEC 60617
IEEE-ANSI
P>
32OP-I-1
P>>
32OP-I-2
93