5.2.8 Power alarm

When it exceeds the setting instantaneous electric power (active, reactive, apparent, active (export),
reactive (export)), pulse output turns on in order to notice.
When it falls below, the output turns off.

5.2.9 Other alarms

Output turns on or off according to each alarm setting.
PF alarm, over frequency alarm, under frequency alarm, voltage harmonics alarm,
current harmonics alarm、voltage THD alarm, current THD alarm, voltage unbalancing alarm,
current unbalancing alarm, power demand alarm, current demand alarm

5.2.10 Output depends on count value

Set the preset value and pulse output turns on the time when count value reaches the preset value.
Refer to the next in detail.

5.2.11 Level output

It runs on or off the output by writing 0 (OFF) or 1 (ON) to the designated data register (OUT1:
DT50294, OUT2: DT50295) via communication by external control.

5.3 Counter function

●Operation mode
Maintain output hold count HOLD
[Output]
[Counting]
[Addition]
0
(1) Output control is maintained after count-up completion and until reset. However counting is
possible despite of count-up completion.
(2) It reverts"0" after counting up full scale, but output control is maintained. However output is OFF
if count value or preset value is changed.
●Change the Preset Value
It is possible to change the preset value even during counting. However note the following points.
◇When the pre-scale value is "1.000".(PSCL=1.000)
(1) If the preset value is changed to the value less than the count value, counting will continue until
it reaches full scale, returns to "0" and then reaches the new preset value.
(2) If the preset value is changed to "0", it will not count up at start with "0". It counts up when the
counting value comes to "0" again (after reach to full scale). However output is OFF if count
value or preset value is changed.
(3) When the count value is fixed, output is changed according to the changing of preset value as
below.
①If the preset value is changed to the value less than the count value or same as count value,
output is ON.
(Count value ≧ Preset value)
②If the preset value is changed to the value more than the count value, output is OFF.
(Count value < Preset value)
◇When the pre-scale is not "1.000". (PSCL≠1.000)
Even if the preset value is changed after counting to full scale, output is not changed.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
OFF
1
2
3
・・・
possible
n-2
n-1
n
ON
n+1
n+2
n+3
n: Preset value