Item
6
CT
7
VT*
8
Over current*
9
Under current*
10
Over Voltage*
11
Under Voltage*
* Common to unit and CH.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Set parameters of CT.
<Range>
Primary side
: 1 to 65535 (initial:5)
Secondary side: 5 (5A), 1 (1A) (initial: 5)
Set parameters of VT when VT is used.
When VT is not used, set parameters of rated voltage to
measure.
<Range>
Primary side
: 100 to 500000 (initial:230)
Secondary side: 100 to 690 (initial:230)
Set a ratio of current for rated current used for threshold to
judge over current.
<Range>
0.0 to 120.0% (initial:0.0)
Set a ratio of voltage for rated voltage used for threshold to
judge over voltage.
< Range >
0.0 to 120.0% (initial:0.0)