Transmission format
Select serial communication (RS485) transmission format (Data length, Parity).
Define the transmission format according to the master's (PLC etc.).
C
- 1
M
Stop bit
Select serial communication (RS485) stop bit.
C
- 1
M
Response time
Set serial communication (RS485) response time of main unit.
When command is received, it sends response after setting response time passes.
C
- 1
M
e s p o n s e
R
* If Data Logger Unit (DLU) or Data Logger Light (DLL) is used as a master, set the response time to
5ms or more because DLU or DLL send the response after 1.1ms or less from receive a command
when transmission speed is set to 19200bps.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Press <ITEM/>>, <SHIFT/∧> to select.
S 4 8 5
O
R
M
F o r
a t
m
[Set list]
8b-o (8bit odd), 8b-n (8bit none), 8b-E (8bit even)
8 b i t - o
Press <ITEM/>>, <SHIFT/∧> to select.
S 4 8 5
O
R
M
S t o p
b i t
[Set list] 1, 2 (initial: 1)
1 b i t
Press <ITEM/>>, <SHIFT/∧> to set.
S 4 8 5
O
R
M
T i
e
[Set range] 1 to 99 ms (initial: 5)
m
5
s
m
SHIFT
ITEM
increase
decrease
(initial: 8b-o)