◆How to connect CT
(1) Power off the measured devices.
(2) Install applicable CT.
(3) Connect CT to the terminal block.
(4) After confirm all wiring correct, turn on the power of the load and KW2M-A.
(Connection example)
◆How to set the parameters for CT
(1) Select CT type (CT-T) according to the using CT.
(Select '5A' if secondary side current of using CT is 5A. Select '1A' if secondary side current
of using CT is 1A.)
(2) Set the primary current of measured CT at primary side current of CT setting mode (CT-1).
< ex > If the measured CT is 400A/1A or 400A/5A, set to"400".
(3) Connect CT according to the CT direction, power side (K) to load side (L).