Wiring with External Devices
This section explains wiring precautions and wiring with external devices of the
AJ65SBT2B-64AD.
4.7.1
To obtain the maximum performance from the functions of the AJ65SBT2B-64AD and
improve the system reliability, an external wiring with high durability against noise is
required.
Precautions for external wiring are as follows:
4
- 10
4.7 Wiring with External Devices
4.7.1 Wiring precautions
Wiring precautions
(a) Use separate cables for the AC control circuit and the external input signals of the
AJ65SBT2B-64AD to avoid the influence of the AC side surges or induction.
(b) Do not install cables together with the main circuit lines, high voltage lines, or
power cables for equipment other than the programmable controller. Noise,
surges, or induction may affect the system.
(c) Ground the shielded wires or shielded cables at one point on the programmable
controller side.
However, depending on the external noise conditions, it may be better to ground
them externally.