Mitsubishi AJ65SBT2B-64AD User Manual page 55

Analog-digital converter module. a melsec
Table of Contents

Advertisement

5
PROGRAMMING
(b) For the ACPU and QCPU (A mode)
CPU module
Device X
X100 to X10F
X110 to X11F
Device Y
Y100 to Y10F
Y110 to Y11F
Device D
D200
D201
D202
D203
Device D
D300
D301
D302
D303
Figure 5.4 Update overview of the CPU module, master module, and AJ65SBT2B-64AD
POINT
Master module
Address
Remote input (RX)
RX00 to RX0F
E0
H
E1
RX10 to RX1F
H
Remote output (RY)
160
RY00 to RY0F
H
161
RY10 to RY1F
H
Remote register (RWw)
1E0
H
1E1
H
1E2
H
1E3
H
Remote register (RWr)
2E0
H
2E1
H
2E2
H
2E3
H
(For the ACPU/QCPU (A mode))
*
In a program example with the RRPA instruction (auto refresh parameter setting) for the ACPU/
QCPU (A mode) (refer to Section 5.6), RWr0 to RWr3 are assigned to D456 to D459.
The devices used in the examples in this chapter may not be available depending
on the CPU module used.
For the available device setting range, refer to the user's manual for the CPU
module used.
For example, X100 or Y100 and the subsequent devices are not available for the
A1SCPU. Use other devices such as B and M.
AJ65SBT2B-64AD
(Station number 1)
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
Remote register (RWw)
RWw0
RWw0 CH1 Average processing setting
RWw1
RWw1 CH2 Average processing setting
RWw2
RWw2 CH3 Average processing setting
RWw3
RWw3 CH4 Average processing setting
Remote register (RWr)
RWr0
RWr0 CH1 Digital output value
RWr1
RWr1 CH2 Digital output value
RWr2
RWr2 CH3 Digital output value
RWr3
RWr3 CH4 Digital output value
5.2 Conditions of Program Examples
1
2
3
4
5
6
5
- 3

Advertisement

Table of Contents
loading