Mitsubishi AJ65SBT2B-64AD User Manual page 75

Analog-digital converter module. a melsec
Table of Contents

Advertisement

5
PROGRAMMING
Initial setting
*1
Changing the initial setting
Processing on completion of the initial setting
Reading a digital output value
Processing in case of an error
Figure 5.20 Program example (when using the ACPU/QCPU (A mode) (FROM/TO instructions)) 2/3
5.7 Program Example When Using the ACPU/QCPU (A mode) (FROM/TO Instructions)
* 1 The program enclosed by the dotted line is required only when changing the initial settings.
CH1 A/D conversion enable/disable
setting (RY00): A/D conversion enable
CH2 A/D conversion enable/disable
setting (RY01): A/D conversion enable
CH1 Input range setting (RY04 to
RYn6): 0 (-10 to 10V)
CH2 Input range setting (RY07 to
RY09): 1 (0 to 5V)
CH1 Average processing setting (RWw0)
: Moving average (16 times)
CH2 Average processing setting (RWw1)
: Count average (16 times)
Initial data processing completion flag
(RY18): ON
Initial data setting request flag (RY19): ON
CH1 A/D conversion enable/disable
setting (RY00): A/D conversion disable
CH2 A/D conversion enable/disable
setting (RY01): A/D conversion disable
Initial data setting request flag (RY19)
: ON
Initial data processing completion flag
(RY18): OFF
Initial data setting request flag (RY19)
: OFF
Reads CH1 Digital output value (RWr0)
to D300
Reads CH2 Digital output value (RWr1)
to D301