SPECIFICATIONS
(7) Initial data processing request flag (RX(n+1)8)
After power-on, this flag turns ON for the AJ65SBT2B-64AD to request an initial data.
When Initial data processing completion flag (RY(n+1)8) is turned on, this flag turns
off.
(8) Initial data setting completion flag (RX(n+1)9)
If Initial data setting request flag (RY(n+1)9) is turned on, this flag turns on after the
initial data setting is completed.
If Initial data setting request flag (RY(n+1)9) is turned off when the initial data setting
is completed, this flag also turns off.
For the timing of turning on/off the remote I/O signal for the initial data setting, refer to
Figure 3.5.
Initial data processing request flag
RX(n+1)8
Initial data processing completion flag
RY(n+1)8
Initial data setting completion flag
RX(n+1)9
Initial data setting request flag
RY(n+1)9
Remote ready
RX(n+1)B
CH
A/D conversion completion flag
RXn0 to RXn3
: Executed by sequence program :
: Performed by the AJ65SBT2B-64AD
Figure 3.5 Operation at initial data setting
3.5.2 Details on each remote I/O signal
3.5 Remote I/O Signals