Resetting Parameters to Factory Defaults

It is possible to reset all parameters to the factory default settings. The ieldbus address is not affected
from the reset command. Also the different maintenance counters are not affected but must be resetted
manually at the UMC100-PAN.
The reset command can be activated via:
UMC100-PAN

Resetting the Password

The password can always be set or disabled using the UMC100 DTM (PBDTM) or using the UMC100-
PAN.

Reading and Resetting Maintenance Counters

Preventive maintenance is the best way to ensure the long service life of any equipment.
The UMC provides several counters which help to better plan maintenance activities or to track down an
existing problem.
Number of motor starts can help to identify worn-out power contacts or to determine on contactor wear
Number of protection trips
Motor operation hours can help to assess the bearing status and its lubrication
The maintenance counters are available at the UMC100-PAN and in the PBDTM.
FieldBusPlug / Issue: 11.009
Code
Source / Root Cause
85
Electronics
9
Wiring, connected meter
has a defect
93
Wiring
94
Wiring
- 99 -
Possible Cause / Suggested Action
An IO module does not respond
during start-up of UMC. See detailed
diagnosis byte to ind out which
module is missing.
Check wiring between UMC and
mod.
Check supply of module
Check status LEDs of the module
Check wiring, short circuit at ana-
logue output
Check Wiring
Check Wiring