Universal Motor Controller
UMC100-FBP
Technical Description
Integration with the GSD File
Besides the physical connection of a device to a PROFIBUS line, the engineering of the whole PROFIBUS
system in the PROFIBUS master is necessary. Every modern PLC (Programmable Logic Controller) or
DCS (Distributed Control System), that can be used as PROFIBUS master, offer the possibility to conig-
ure and parameterise devices connected to the master.
Electronic data sheets are used as a basis. In the PROFIBUS world these electronic data sheets are
called GSD iles. Within such a ile all properties relevant for operation of the slave are described (e.g.
supported baud rates, max. number of modules etc.).
The GSD ile ABB_0A09.GSD (for PDQ) and ABB_34E0.GSD (for PDP) are contained in the software
Engineering Package
PBE91-FBP.010x 1SAJ94091R010x.ZIP
The ZIP ile can be obtained from ABB's web site (http://www.abb.de -> Control Products and Systems)
or on the FBP System CD (CDC 190 008 E04xx). Please ask your local sales ofice for it.
Integration with the Device Type Manager (DTM)
In addition to the option of integrating devices with GSD iles more and more modern control systems
support the FDT/DTM concept. FDT (Field Device Tool) technology standardises the communication inter-
face between ield devices and systems.
For the UMC100 (and also other FBP devices) a DTM is available which can be ordered separately. Con-
sult the PBDTM manual for more information.

Using the UMC100 in a DeviceNet Network

DeviceNet is based on the Controller Area Network (CAN) technology and mostly used in the Americas.
To integrate the UMC100 into a DeviceNet network use the DNP1-FBP FieldBusPlug. The igure below
shows the sketch of a DeviceNet line with DNP1-FBP, two UMC100s and available accessories. More
details are available in the technical manual of the DNP1-FBP.
24VDC
UMC100-FBP
The UMC100 can be parameterised using the GSD ile. But due to parameter length
limitations only the most important parameters can be conigured with the GSD ile
in the event that the PDQ is used. For PDP this limitation does not exist.
For creating a customer-speciic application the DTM must be used! Parameterisa-
tion of the control and protection parameters can also be carried out with the GSD
ile only.
AC500
CPU
with
DeviceNet
Master
DNF11
UMC with
FieldbusPlug
DNP21
UMC
24VDC
- 4 -
UMC with
FieldbusPlug
DNP21
UMC
DNR11 Bus
Termination
24VDC
FieldBusPlug / Issue: 11.009
V 6