Control Function Actuator 1 - 4 - ABB UMC100-FBP Technical Description

Fieldbusplug
Hide thumbs Also See for UMC100-FBP:
Table of Contents

Advertisement

Universal Motor Controller
UMC100-FBP
Technical Description

Control Function Actuator 1 - 4

Use this function in a feeder that requires the operation of an actuator that opens/closes e.g. a valve.
Please note that the actuator operation mode is not able to keep a valve at a certain setpoint.
UMC-
PAN
Fieldbus
Plug
Control function = Actuator  (Basic circuit)
The control functions Actuator 1, , 3 and 4 provide different use of and reaction to the limit switches
"Closed" and "Open" as well as the torque switches. The switches must be connected in a predeined
manner to DI0, DI1 and DI3.
Optionally terminals named 4VDC Out (1) or DO can be used as a fault output
UMC100-FBP
The voltage dip function is not supported and checkback via DIO is not supported in
these control functions.
Set the following parameters as listed here:
- Inv DI start input = No
- Inv DI stop input = No
- Inching DI start input (Jog) = Yes
- Multifunction 0/1 = Off
- Checkback: Current or Simulation (test purposes only)
- Adjust Time Limit Actuator
GND
(24VDC)
24VDC
DO3
12
I
10 11
0V
24VDC
Contactor
Supply
(e.g. 230VAC)
K1
DOC DO0
DO1
5
7
8
UMC100
Lim
13 14
15
16
17
DI0
DI1 DI2 DI3 DI4 DI5
Limit
Limit
Closed
Open
Torque
Open/
Closed
- 7 -
L1, L2, L3
K2
DO2
9
3
18
Close
k1
Open
k2
M
FieldBusPlug / Issue: 08.009
V 6
K1=Open
K2=Close