Universal Motor Controller
UMC100-FBP
Technical Description
Control Function Overload Relay
The UMC100 parameterised with the control function 'Overload relay' can be used to replace a standard
overload relay.
The outputs DO ... DO3 and the inputs DI0 ... DI5 are directly connected to the ieldbus and not used
from the control function.
If a fault output is activated the fault output (DO or 4 V DC Out DO3) cannot be controlled from the
ieldbus anymore but is controlled by the UMC itself.
After powering up, contact DO0 immediately closes and contact DO1 opens.
UMC-
PAN
Fieldbus
Plug
Circuit diagram of the UMC overload relay mode.
Fault Behaviour:
•
Contact DO0 opens
•
Contact DO1 closes
•
The fault output DO/DO3 is activated if conigured
•
The monitoring signal FAULT is sent to the ieldbus
•
The red LED on the UMC is switched on
•
The FAULT signal on the control panel lashes.
UMC100-FBP
The following features are not supported in this control function:
•
Checkback supervision
•
UMC controlled starting and stopping (bus, LCD, DI)
•
Simulation and stop via multifunction inputs
•
Bus fault reaction
•
Voltage dip
GND
(24VDC)
24VDC
DO3
12
I
Lim
10 11
0V
24VDC
Contactor
Supply
(e.g. 230VAC)
K1
k1
On
Off
DOC DO0
DO1
DO2
5
7
8
9
UMC100
13 14
15
16
17
18
DI0
DI1 DI2 DI3 DI4 DI5
- 58 -
V 6
L1, L2, L3
3
k1
M
FieldBusPlug / Issue: 08.009