Table 6- 7
Technical specifications for the dv/dt filter plus Voltage Peak Limiter, 500 V – 600 V 3 AC, Part 3
Order number
Suitable for Power Module
Type rating of the Power
Module
I
thmax
Degree of protection
du/dt reactor
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- to the Power Module
- Load
- PE
Max. permissible cable
length between du/dt reactor
and motor
Dimensions
Width
Height
Depth
Weight, approx.
Voltage peak limiter
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- to the du/dt reactor
- DC
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Two du/dt reactors are required for these du/dt filters. The technical data provided applies to one du/dt reactor.
1)
Note
Cable lengths for versions with two du/dt reactors
For versions with two dV/dt reactors, the cable lengths specified in the table do not change.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E00692302A
6SL3000-
2DH38-1AA0
6SL3310-
1GF38-1AAx
kW
560
A
810
IP00
kW
0.828
kW
0.867
kW
0.927
2 x M12
2 x M12
M6
m
mm
445
mm
385
mm
312
kg
160
kW
0.106
kW
0.1
kW
0.091
M10
M10
M8
mm
309
mm
1312.5
mm
400
kg
72
1
300 (shielded)
450 (unshielded)