Emerson Rosemount 5708 3D Solids Scanner DeltaV Series Manual Supplement page 30

Integration
Table of Contents

Advertisement

Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
2. Command line breakdown:
Command Line
\\usrtc-smartlab1
C
\program files
(x86)\3DVisionEmrsn\binclient\bin\
visualvision3dviewer .exe
\\usrtc-smartlab1\c\3dvision
1
vbNormalFocus
taskkill.exe /im
visualvision3dviewer.exe
Testing
1. Once the script is entered, close Microsoft Visual Basic, save and close the graphic file.
2. Press the Run button
3. Select the new button and the 3D image window will open and the image will load. You will be able
to maneuver the image with the mouse.
30
Definition
Name of server
Shared drive that contains 3DVision Server software program files
Path to software
Image display program. There must be a space after .exe!
Location of image file as entered in 3DVision software server but in the
format \\server\share\folder path
image file name, same as SCADA ID
Causes the image window to display in the foreground.
Ends the image program when it is called again if the operator does not
close it. The prevents multiple windows from being open in the
background where the operator cannot get to them to close them.
in DeltaV Operate Configure and open the desired operator graphic.
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
Manual Supplement
00809-0300-4570, Rev BA

Advertisement

Table of Contents
loading

Table of Contents