Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
19. All of the parameters in DeltaV are now set. To send this configuration to the DeltaV controller, I/O
under the expanded controller menu must be right-clicked. Select Download -> I/O to begin the
configuration download.
20. Right-click on Added device and select Diagnose to verify the communication status. Select a
dataset and double-click on StrtRegAddr to verify the values of the registers.
22
Table 1-4. Configuration for Two Datasets that Display a 3D Solids Scanner's 13
Parameters
Parameter
DeltaV data type
PLC data type
PLC register offset
Number of values
Dataset 1
16 bit unit w/Status
Holding registers
0
24
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
Manual Supplement
00809-0300-4570, Rev BA
Dataset 2
String w/Status
Holding registers
24
2