Manual Supplement
00809-0300-4570, Rev BA
Example setup for dataset constructed to read the first 12 parameters
DeltaV tab. Setup DeltaV data type as 16 bit unit w/Status.
Example setup for dataset constructed to read the "Tag Name" parameter
DeltaV tab. Setup DeltaV data type as String w/Status.
Note
The Dataset Tag can be modified to facilitate the data management.
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
b. On the DeltaV tab, in the DeltaV data type list, select the appropriate data type for the values
which are to be retrieved. See figures on
first 12 parameters
and
parameter
below.
DeltaV data type: Enter the appropriate data type for the values which are to be retrieved.
i. Select 16 bit unit with status: use for the first 12 parameters in registers 40001-40024.
It will be referred to as Dataset1.
ii. Select String with status: use for the 'Tag Name' parameter in registers 40025-40026. It
will be referred as Dataset2.
c. On the PLC tab use the following settings:
i. PLC data type: holding registers (apply for both Datasets properties)
ii. PLC register offset: Enter the start address. For example, if the first value should be 'Avg
Distance', enter 0. If the first value should be Avg. Level, enter 16.
iii. Number of values: Enter the desired number of values to read. Note that to read each
parameter (Avg. Distance, Min Distance, Max Distance, etc.), two values are required.
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
Example setup for dataset constructed to read the
Example setup for dataset constructed to read the "Tag Name"
PLC tab. Setup the PLC data type as holding registers, PLC
register offset as 0, and Number of values as 24.
PLC tab. Setup the PLC data type as holding registers, PLC
register offset as 24, and Number of values as 2.