Using Direct Connection To Deltav With A Serial Card - Emerson Rosemount 5708 3D Solids Scanner DeltaV Series Manual Supplement

Integration
Table of Contents

Advertisement

Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
19. If a multidrop connection is desired, each scanner should be linked with a device instance under the
associated virtual serial port. Additionally, the required Datasets should be created. Repeat
through
the physical devices.
20. All parameters in DeltaV are now set. To send this configuration to the DeltaV controller, I/O under
the expanded controller menu must be right-clicked. Select Download -> I/O to begin the
configuration download.
Note
Anytime a download to the controller or any of the cards occurs, the 3DMultiVision server will stop communicating
with DeltaV. The server must be restarted or the SCADA Definition window must be opened and OK'd to see values on
DeltaV. The SCADA Definition can be found in the 3DVision application under Tools > Server Options > SCADA
Configuration. Open the SCADA Definition and select OK.
Figure 1-5. Download the Configuration
1.4

Using direct connection to DeltaV with a serial card

If a direct connection to a DeltaV serial card is desired, the byte order will need to be manipulated in
DeltaV to see the correct values. The 3D Solids Scanner's byte sending order is high to low; DeltaV
assumes the byte sending order is low to high.
The serial card is one of the card types in the DeltaV Explorer and is therefore configured like any other
card. Each serial card has two ports, and each port can support as many as 16 serial devices.
14
17
to add each device; choose the appropriate Device Address to match the addresses of
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
Manual Supplement
00809-0300-4570, Rev BA
steps14