Importing And Exporting Of Settings; Exporting Settings; Importing Settings - ABB RELION REX640 Operation Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 5
Using Web HMI
5.19
5.19.1
5.19.2
78

Importing and exporting of settings

The relay's setting parameters can be imported and exported in the XRIO file format.

Exporting settings

The relay's setting parameters can be exported in XRIO file format.
1.
Select Import/Export on the menu bar.
2.
Select Import/Export Settings from the drop-down list.
3.
Click Export Settings.
The export file includes all parameters except status parameters and parameters
writable only in LHMI.
GUID-E45F4AA1-A30F-48F9-8AD6-1E4B349A5318 V1 EN
Figure 74:
Exporting settings
4.
Click Save to export the settings to the computer.

Importing settings

The parameter export and import function can be used, for example, when the
protection relay's parameters are set using the WHMI instead of PCM600. The
protection relay's settings engineered with PCM600 can be exported to XRIO files and
imported to the WHMI. The WHMI can be used to write the settings to the protection
relays. The WHMI can also be used to read the protection relay's setting parameters
and to export those to files, which can be used by PCM600. WHMI imports all
parameters from the import file except lockable and read-only parameters.
The XRIO file name supports only characters A-Z, a-z and 0-9.