Section 7
Commissioning
7.6
126
Select Testing and Commissioning/Test mode/IED blocked or IED test and
blocked to activate the IED blocked mode and the IED test and blocked mode.
Table 23:
Test mode
Test mode
Description
Normal mode
Normal operation
IED blocked
Protection works as in "Normal mode"
but the ACT configuration can be used
to block physical outputs to process.
Control function commands are
blocked.
IED test
Protection works as in "Normal mode"
but protection functions work in parallel
with test parameters
IED test and
Protection works as in "Normal mode"
blocked
but protection functions work in parallel
with the test parameter. The ACT
configuration can be used to block
physical outputs to process. The control
function command is blocked.
If the IED blocked or IED test and blocked mode is not cancelled, it
remains on and the Home button remain flashing.

ABB Product Data Registration

The ABB Product Data Registration feature traces composition changes in the
protection relay's SW or HW. Traceability allows better support and maintenance
possibilities.
After a composition change, an LCT indication is seen on the LHMI at the protection
relay start-up. PCM600 reads the changed data from the protection relay.
Therefore a connection to the protection relay must be established first. Composition
data can be read with PCM600 by enabling LCT during PCM600 installation and
activating collection in PCM600 from the Lifecycle Handling menu. For detailed
information, see PCM600 online help.
The LCT indication is cleared in the same way as other indications. If composition
data is not collected with PCM600, the indication reappears after protection relay's
reboot.
If the LCT indication appears, update the protection relay
composition to avoid information mismatch. The LCT indication does
not affect the functionality of the protection relay.
1MRS759118 A
Protection
Protection
BEH_BLK
BEH_TST
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
TRUE
Operation Manual
REX640