The Parameter List page offers filtering functionality where only chosen
parameters are displayed, saved or printed. There are various options for
filtering.
Enabled Settings hides settings of disabled function blocks. This option
is checked by default.
Writable settings displays only writable settings.
Basic settings displays only basic settings.
Setting group displays only the settings of the selected setting group.
Options can be combined. For example, with the Enabled Settings and
Writable settings selected, only enabled and writable settings are displayed.
5.
Click Export and select text (.txt) or comma separated values (.csv) file format
to save the settings.
6.
Click Print to print all the selected parameters.

Editing values

1.
Select Parameters on the menu bar.
2.
Click a submenu in the left navigation bar to see the function blocks.
3.
Click a function block to see the setting values.
4.
Click Enable Edit.
If the edit mode is enabled accidentally, click Disable Edit.
Editing cannot be disabled when a value has already been
written to the protection relay. After clicking Write to Relay,
click either Reject Changes or Store Changes.