Section 7
Commissioning
7.5.2.4
124

Checking SMV data

1.
On the SMV Receiving page, check the sampled values data that the relay
subscribes from the Ethernet network.
The left side of this page shows a list of devices that send SMV messages to the
relay. These devices that publish data for the relay are defined in the relay
configuration. The right side of the page shows the SMV data that the relay
receives from the network. The data set consists of value and quality attributes.
The received data has status indicators where green means all OK, yellow
warning and red error.
GUID-3F5F8BB4-025E-4710-A6BD-2E07E40B0CDB V1 EN
Figure 108:
SMV Receiving page
2.
On the SMV Sending page, check the status of the relay's configured SMV
control blocks and the values of the sent IEC 61850-9-2 sampled value data.
The left side of this page shows a list of the devices where the relay sends SMV
messages. In the system there may be more devices, but these devices are
according to relay configuration the ones subscribing the data from the relay.
The right side of the page shows the SMV data the relay sends to the network.
The sent data has status indicators where green means all OK, yellow warning
and red error.
1MRS759118 A
REX640
Operation Manual