Checking Binary Input And Output Circuits; Checking Binary Input Circuits; Checking Binary Output Circuits - ABB RELION REX640 Operation Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 A
7.2.4
7.2.4.1
7.2.4.2
REX640
Operation Manual
Correct possible errors before continuing to test the circuitry.
Test the circuitry.
Polarity check
VT circuit voltage measurement (primary injection test)
Earthing check
Phase relationship
Insulation resistance check
The polarity check verifies the integrity of circuits and the phase relationships. The
polarity must be measured as close to the protection relay as possible.
The primary injection test verifies the VT ratio and the wiring all the way from the
primary system to the protection relay. Injection must be performed for each phase-to-
neutral circuit and each phase-to-phase pair. In each case, voltages in all phases and
neutral are measured.

Checking binary input and output circuits

Checking binary input circuits

Preferably, disconnect the binary input connector from the binary input cards.
Check all the connected signals so that both the input level and the polarity are in
accordance with the protection relay specifications.
Do not use AC voltage. Binary inputs are rated for DC voltage only.

Checking binary output circuits

Preferably, disconnect the binary output connector from the binary output
cards.
Check all connected signals so that both load and voltage are in accordance with
the protection relay specifications.
Section 7
Commissioning
99