Daikin Maverick II MPS062E Installation And Maintenance Manual page 87

Commercial packaged rooftop system
Table of Contents

Advertisement

Dehum Set-Up
Defrost Set-Up
Dehum Method= None
Defrost State= _________
RH DB= 2%
Manual DF= No
Dewpoint DB= 2°F
MinCmpOpTm= 10min
RH Period= 30s
MinAccCmpTm= 40min
RH Gain= 1
MaxFrostTm= 120min
RH PAT= 30s
Defrost Temp= XXºF
RH Max Chg= 10%
Tdef Adj= 0.0ºF
RH Stg Time= 10min
CmpOpTm= XXXmin
Stg Rht DB= 5.0°F
AccCmpOpTm= XXXmin
Dehum Ctrl= Occupied
LoFrstAccTm= XXXmin
Sensor Loc= Return
HiFrstAccTm= XXXmin
Mn Lvg Coil T= 45.0°F
Mx Lvg Coil T= 52.0°F
Rht Cmp Lmtg= Yes
Min Rheat Spt= 55.0°F
Max Rheat Spt= 65.0°F
RH Sens Type= VDC
RH Min Sig= 0.0V
RH Max Sig= 10.0V
Min Dehum Spd= 33%
Max Dehum Spd= 100%
Rht Min Pos= 10% (RPS)
RH Dec Rate= 1
RHOutMaxV= 10
www.DaikinApplied.com
Energy Rec Set-Up
Energy Rcvy= Yes
ER Wheel= ___________
Wheel Speed= XXX%
Whl Spd Cmd= XXX%
ER LAT= XXX°F
ER EAT= XXX°F
Min ExhT Diff= 2.0°F
Max ExhT Diff= 6.0°F
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
Rel Humidity= XXX%
Min Whl Spd= 5%
Intersect Pt= XXX.XºF
Fst Mgnt Meth= Timed
OA Frst Temp= -20.56°F
Defrost Time= 5min
Defrost Period= 60min
Defrst On Tm= 1s
Defrst Off Tm= 24s
ER Whl Period= 30s
ER Whl Gain= 1.0
ER Whl PAT= 30s
15% (MPS)
ER Max Chg= 10%
5% (DPS, DPH)
LoERLATCmpLk= 45.0°F
87
MicroTech III Controller Operation
Head Pressure Set-Up
Wtr Reg Vlv= XXX%
Head P Circ 1= XXXPSI
Head P Circ 2= XXXPSI
Setpoint= 260PSI
Head Press DB= 10PSI
WRV Period= 10s
WRV Gain= 3.6
WRV PAT= 10s
WRV Max Chg=7%
WRV Init Tm= 60s
Min WRV Pos=10%
Min WRV Tmp= 58°F
Max WRV Tmp= 150°F
WRV Act Time= 60s
Min WRV Time= 60s
IM 991-2 • MAVERICK II ROOFTOP