Daikin Maverick II MPS062E Installation And Maintenance Manual page 113

Commercial packaged rooftop system
Table of Contents

Advertisement

Select Yes or No. If not applicable to the type of unit, select N/A.
I. INITIAL CHECK
A. Is any shipping damage visible? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
B. Are fan drives properly aligned and belts properly adjusted? . . . . . . . . . . . . . . . . . . . . . . . . . Yes
C. Tightened all setscrews on pulleys, bearings and fans? . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
D. Have the hold-down bolts been backed off on spring mounted fan isolators? . . . . . . . . . . . . . . . . . Yes
E. Do fans turn freely? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
F. Has the discharge static pressure reference line been properly located within the building? . . . . . . . . . Yes
G. Electrical service corresponds to unit nameplate? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
G1. Voltage at Terminal Block | Disconnect
H. Is the main disconnect adequately fused and are fuses installed? . . . . . . . . . . . . . . . . . . . . . . Yes
I. Are crankcase heaters operating, and have they been operating 24 hours prior to start-up? . . . . . . . . . Yes
J. Are all electrical power connections tight? (Check compressorelectrical box.) . . . . . . . . . . . . . . . . Yes
K. Is the condensate drain trapped? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
II. FAN DATA
A. Check rotation of supply fan? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
B. Voltage at supply fan motor: . . . . . . . . . . . . . . . . 1–2_____________ V
C. Supply fan motor amp draw per phase: . . . . . . . . . . . . . . . L1 _____________
D. Fuse sizes: . . . . . . . . . . . . . . . . ._______________________________________________________________________
E. What is the supply fan rpm? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________
F. Check rotation of return fan?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
G. Voltage at return fan motor: . . . . . . . . . . . . . . . . 1–2_____________ V
H. Return fan motor amp draw per phase: . . . . . . . . . . . . . . . L1 _____________
I. Fuse sizes: . . . . . . . . . . . . . . . . ._______________________________________________________________________
J. What is the return fan rpm? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________
K. Record supply static pressure at unit in inches of H
L. Record return static pressure at unit (with outside air dampers closed) in inches of H
13F-4158 (06/17)
www.DaikinApplied.com
Rooftop Equipment Warranty Registration
Rooftop Equipment Warranty Registration Form (continued)
1–2_____________ V
0: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________
2
113
2–3 _____________ V
1–3 _____________ V
2–3 _____________ V
1–3 _____________ V
L2 _____________
L3 _____________
2–3 _____________ V
1–3 _____________ V
L2 _____________
L3 _____________
0: . . . . . . . . . . . . . . . _____________
2
IM 991-2 • MAVERICK II ROOFTOP
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
No
N/A
2