Cooling
Economizer
Occ Clg Spt= 72.0°F
OAD/Econo Pos= XXX%
Unocc Clg Spt= 85.0°F
DAT Clg Spt= 55.0°F
DAT Clg Spt= 55.0°F
Min OA Pos= XXX%
FreeClgStatus = _______
Occ Clg Spt= 72.0°F
Unocc Clg Spt= 85.0°F
www.DaikinApplied.com
Min OA Damper
Heating
Min OA Pos= XXX%
Occ Htg Spt= 68.0°F
Vent Limit= 20%
Unocc Htg Spt= 55.0°F
LoFlo V Lmt= 30%
MWU Spt= 70.0°F
DCV Limit= 10%
DAT Htg Spt= 85.0°F
Min OA Src= __________
83
MicroTech III Controller Operation
Dehumidification
Date/Time/Schedules
Dehum Status= ________
Time= hh:mm:ss
Rel Humidity= XXX%
Date= MM/DD/YY
Dewpoint= XXX°F
UTC Diff= -60min
Dehum Method= None
RH Setpoint= 50%
Mon= HH:MM-HH:MM
Dewpoint Spt= 50°F
Tue= HH:MM-HH:MM
Reheat Spt= XXX°F
Wed= HH:MM-HH:MM
Reheat Cap= XXX%
Thu= HH:MM-HH:MM
Fri= HH:MM-HH:MM
Sat= HH:MM-HH:MM
Sun= HH:MM-HH:MM
Hol= HH:MM-HH:MM
Hol 1=MMMDD/YY-MMMDD/YY
Hol 2=MMMDD/YY-MMMDD/YY
Hol 3=MMMDD/YY-MMMDD/YY
Hol 4=MMMDD/YY-MMMDD/YY
Hol 5=MMMDD/YY-MMMDD/YY
Hol 6=MMMDD/YY-MMMDD/YY
Hol 7=MMMDD/YY-MMMDD/YY
Hol 8=MMMDD/YY-MMMDD/YY
Hol 9=MMMDD/YY-MMMDD/YY
Hol 10=MMMDD/YY-MMMDD/YY
Beg= MMMDD/YY@HH:MM
End= MMMDD/YY@HH:MM
OPTIMAL START
Enable= No
Htg Range= 0.4 ºF/min
Htg OAT= 35 ºF
Des Htg OAT= 0 ºF
Clg Rate= 0.4 ºF/min
Clg OAT= 85 ºF
Des Clg OAT= 95 ºF
DAYLIGHT SAVINGS
DLS Strt Mon= Mar
DLS Strt Wk= 2nd Week
DLS End Mon= Nov
DLS End Wk= 1st Week
DLS Enable= Auto
PURGE
Max Purge= 0min
IM 991-2 • MAVERICK II ROOFTOP
DAILY SCHEDULE
HOLIDAY DATES
ONE EVENT SCHEDULE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents