Mitsubishi Electric MELSEC-Q Series User Manual page 48

Qcpu a mode, cpu module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(2) MELSECNET (II) and MELSECNET/10 modules
(a) Use a double-shielded coaxial cable for the MELSECNET
module which uses coaxial cables such as A1SJ71AR21,
A1SJ71LR21 and A1SJ71BR11. Noise in the range of 30 MHz
or higher in radiation noise can be suppressed by the use of
double-shielded coaxial cables (manufactured by MITSUBISHI
CABLE INDUSTRIES, LTD: 5C-2V-CCY). Earth the outer
shield to the ground.
For the shield grounding, refer to item (1).
(b) Make sure to attach a ferrite core to the double-shielded
coaxial cable connected to the MELSECNET module. In
addition, position the ferrite core on each cable near the outlet
of the control panel. The ferrite core manufactured by TDK
Corporation, ZCAT3035-1330, is recommended.
(3) Ethernet module
Precautions for using AUI cables, twisted pair cables and coaxial
cables are described below.
(a) Always earth the AUI cables
connectors. Because the AUI cable is of the shielded type,
strip part of the outer cover and earth the exposed shield
section to the ground on the widest contact surface as shown
below.
Refer to (1) for the earthing of the shield.
*1 Make sure to install a ferrite core for the cable.
The ferrite core manufactured by TDK Corporation, ZCAT2032-
0930, is recommended.
Earth here
Shield
AUI cable
Shield
14
*1
connected to the 10BASE5