Performance List (Continued)
Item
Latch (power failure
compensation) range
Remote RUN/PAUSE contact
Clock function
Allowable momentary power
interruption time
5VDC internal current
consumption
Weight
External dimensions
CAUTION
When using the conventional type peripheral device and GPP function software package,
set the programmable controller type to "Q02(H)-A/Q06H-A".
When the GPP used is incompatible with the "Q02(H)-A/Q06H-A", make the following
setting.
GPP-
Compatible CPU
Programmable
controller type
Note that the setting of the programmable controller type to "A3ACPU" or "A3HCPU" will
limit the usable ranges of the devices.
Q02CPU-A
Defaults to L1000 to L2047
(Latch range can be set for L, B, T, C, D and
W)
One RUN contact and one PAUSE contact
can be set within the range from X0 to
X1FFF.
Year, month, day, hour, minute, second,
day of week (Automatically recognizes leap
years.)
Accuracy
-3.18 to +5.25s(TYP.+2.12s)/d at 0°C
-3.93 to +5.25s(TYP.+1.90s)/d at 25°C
-14.69 to +3.53s(TYP.-3.67s)/d at 55°C
Depends on power supply module
0.60A
0.20kg
98(3.86)(H)×27.4(1.08)(W)×89.3(3.52)(D)
"Q02(H)-A/Q06H-A"-
Incompatible
A4UCPU
6
Type
Q02HCPU-A Q06HCPU-A
0.64A
0.64A
0.20kg
0.20kg
mm(inches)
"A4UCPU"-
Incompatible
A3ACPU
Remarks
Set range in
parameters
Parameter
setting
"A3ACPU"-
Incompatible
A3HCPU