Error
Error
Code
Massage
(D9008)
"LINK
PARA.
47
ERROR"
Table 6.1 Error Code List (Continue)
Detailed
Error
CPU
Code
States
(D9091)
[When using
MELSECNET/(II)]
(1) When the link range
0
Stop
or
(2) The total number of
Contin
ue (set
by
(3) The head I/O
param
eter)
[When using
MELSECNET/10]
(1) The contents of the
470
(2) The network refresh
(3) The head I/O
Error and Cause
at a data link CPU
which is also a
master station
(station number =
00) is set by
parameter setting at
a peripheral device,
for some reason the
data written to the
link parameter area
differs from the link
parameter data read
by the CPU.
Alternatively, no link
parameters have
been written.
slave stations is set
at 0.
number of the
network parameters
is incorrect.
network refresh
parameters written
from a peripheral
device differ from the
actual system at the
base unit.
parameters have not
been written.
number of the
network parameters
is incorrect.
106
Corrective Action
(1) Write the parameters
again and check.
(2) Check the station
number settings.
(3) Check the head I/O
number of the
network parameters.
(4) Persistent error
occurrence may
indicate a hardware
fault. Consult your
nearest Mitsubishi
representative,
explaining the nature
of the problem.